Permit: T07CM02234

Parcel: 13316030E

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM02234

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/09/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
CONTRACTOR TO FINISH #3 & 4 OF PREVIOUS INSPECTION
AND STRAP M/C ABOVE PANEL
07/06/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL CONDUCTORS UNDER SCREW TERMINALS IN A CLOCKWISE DIRECTION OF 3/4 OF A TURN
2. INSTALL ALL PLATES
3. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20 - FLUSH ON COMBUSTIBLES
4. TIE WIRE IS NOT APPROVED FOR CEILING SUPPORTS
OF VDV CABLES ALSO, INSTALL AS PER 300.11 ATTACHED
BOTH ENDS 725.6 & 800.6
5. NEED ACCESS TO ELECTRICAL PANELS