Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM02234
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/09/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* CONTRACTOR TO FINISH #3 & 4 OF PREVIOUS INSPECTION AND STRAP M/C ABOVE PANEL |
|
07/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL CONDUCTORS UNDER SCREW TERMINALS IN A CLOCKWISE DIRECTION OF 3/4 OF A TURN 2. INSTALL ALL PLATES 3. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20 - FLUSH ON COMBUSTIBLES 4. TIE WIRE IS NOT APPROVED FOR CEILING SUPPORTS OF VDV CABLES ALSO, INSTALL AS PER 300.11 ATTACHED BOTH ENDS 725.6 & 800.6 5. NEED ACCESS TO ELECTRICAL PANELS |