Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T07CM02215
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/05/2007 | FRAMING | Approved | IVRS - Inspection :* | |
11/02/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FIRESTOP AT LAUNDRY ROOM IN DROPPED CEILING 2) GAS LINE FOR DRYER CALLS FOR 3/4 ?-PE 3) NO DWV TEST ON GARAGE PART OF HOUSE 4) MISSING PROTECTION PLATES ON PLUMBING LINE THRU-OUT BOTH UNITS 5) STRAPPING MECHANICAL BATH VENT NEEDS TO BE ADJUSTED 6) ACCESSABILITY FOR MECHANICAL DAMPER NEEDS TO BE MADE MORE ACCESSIBLE 7) WILL REINSPECT GAS PRESSURE TEST AFTER GAS LINE IS CORRECTED |
|
10/23/2007 | FRAMING | Partial Approval | IVRS - Inspection :* | |
10/22/2007 | FRAMING | Cancelled | IVRS - RI canceled | |
10/18/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CLIPS NEED TO BE NAILED PROPERLY AT STAIRWAY |
|
10/17/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING CLIPS PER DETAIL 11/A-6 AND 1/A-5 ON STAIRS |