Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 11/15/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 11/14/2007 | PLUMBING - FINAL | Cancelled | ||
| 11/13/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NON CARBONATED BEVERAGES REQUIRE SEPERATE BACKFLOW PROTECTION-LOCATED UPSTREAM OF RP. INSTALL UNION ON RP 2) PROVIDE ACCESS TO TRAP PRIMERS AND HAMMER ARRESTORS 3) CAULK SINK 4) ONLY 1 SLIP NOT ALLOWED ON STEM OF P TRAP 5) SUPPORT MIXING VALVES 6) CANNOT REDUCE DRAIN SIZE AT ICE MAKER. ALSO PVC PIPING REQUIRES PRIMER 7) PLAN REQUIRES PRIMER 8) PLAN REQUIRES PRIMER ON CPVC WATER PIPING 9) EXPOSE CLEANOUT AT HS NEAR HOOD 10) BACTERIA REPORT RECEIVED 11) LIST MAY NOT BE COMPLETE 12) AFTER HOURS INSPECTION |