Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM02182
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/10/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK FOR FINAL |
|
07/18/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* COMPLETE ITEM #2 FROM INSPECTION ON 7/6/07 BONDING SCREW TO BE THREADED INTO BACK OF ENCLOSURE NOT JUST NUTTED FIELD 2 ONLY |
|
07/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COMPLETE ITEM #3 FROM INSPECTION ON 7/2/07 2. GROUND BAR IN DISCONNECT SWITCHES TO BE ELECTRICALLY CONNECTED TO ENCLOSURE. INSTALL BONDING SCREW CHECK DIRECTIONS ON DISCONNECT COVER. |
|
07/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL BONDING BUSHINGS ON OPEN ENDS OF CONDUIT IN HAND HOLE ENCLOSURE -- NEC 250.4 2. SPLICES IN UNDERGROUND HAND HOLE ENCLOSURE TO BE LISTED FOR WET LOCATION -- NEC 314.30 3. GROUNDING ELECTRODE CONDUCTOR TO BE BONDED TO BOTH ENDS OF METAL CONDUIT IT IS INSTALLED IN NEC 250.64 4. UNCOVER GROUND ROD 5. ATTACH BOX COVER TO BOX (UNDER GROUND BOX) 6. PROVIDE LADDER FOR INSPECTION |