Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/05/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/28/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK UNITS SUBJECT TO OTHER INSPECTIONS ALSO, WAITING ON PLAN REVISIONS |
|
| 09/26/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. CABLE SHEATHING TO EXTEND 1/4" INTO ENCLOSURE 2. PROPERLY GROUND LIGHTS 3. GFI NOT WORKING #180 KITCHEN 179, 173, 172, 171 4. CLEAN FOREIGN MATERIAL FROM BUSS #180 OK 1ST FLOOR PANELS EX 180 |
|
| 09/25/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PROTECT CABLE AND SECURE TO BACK PLATE OF BATH LIGHT 2. EXPOSED CONDUCTOR TO DRYWALL - A BOX IS NEEDED BEHIND LIGHT 3. PANEL DIRECTORY TO BE AS PER 408.4 - NO ABBREVIATIONS 4. CLEAN EXCESS DIRT FROM PANEL |
|
| 09/24/2007 | ELECTRIC - FINAL | Partial Approval | OK UNITS #186, 274, 275, 277 279 | |
| 09/21/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED |