Permit: T07CM02163

Parcel: 12401010A


Addresses:

1035 N MOUNTAIN AV

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
07/02/2007 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
1. PROTECT WATER PIPING IN WATER HEATER ROOM FROM HITTING METAL PIPING
2. COMPLETE 2" CLEANOUT OUTSIDE BUILDING
3. OK UNDER FLOOR PER REDLINE
06/20/2007 PLUMBING - ROUGH, SOIL Not ready for Inspection PLEASE POST YOUR ADDRESS
1. PLUMBER HAS EXCEEDED THE WORK PRESCRIBED ON THE PLAN. NO REDLINES ON SITE.
2. ALL MATERIALS TO CONFIRM TO RECOGNIZED STANDARDS SEE 301.1 2003 UPC
3. PLAN CALLS FOR A MOP SINK. YOU HAVE INSTALLED A SHOWER VALVE. SLIP JOINT NOT APPROVED UNDER FLOOR MISSING CLEANOUT NOT SUPPORTED.
4. ALL PIPING TO BE SUPPORTED TO TABLE 3-2 2003 UPC
5. DIELECTRIC UNIONS TO BE INSTALLED IN ACCESSIBLE AND VISIBLE LOCATIONS.
6. HOT PIPING REQUIRES INSULATION. ALL STUB-OUTS TO BE SECURED.