Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T07CM02157
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/03/2007 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1. FINISH DRYER VENT PENETRATION THRU ROOF - WILL CHECK ON FINAL 2. PLEASE PROVIDE A LETTER OF PERMISSION FROM TRANE TO ALLOW UP TO 30' OF CONDENSATE PIPE BEFORE THE TRAP 3. TIE WIRE NOT APPROVED FOR CLAMPING PIPE 4. OK FOR CEILING TILES. LEAVE OUT AROUND EACH FAN COIL 5. ADDRESS SECONDARY DRAIN LOCATIONS |
|
06/13/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE 90 DEGREE ELBOWS ON SECONDARY DRAINS 2) PROVIDE A MIN 100 PSI HYDROSTATIC TEST ON ALL HYDRONIC PIPING 3) SUSPENDED ROUGH OK TO PROCEED WITH CEILING GRID |