Permit: T07CM02157

Parcel: 11011181B

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T07CM02157

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/03/2007 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1. FINISH DRYER VENT PENETRATION THRU ROOF -
WILL CHECK ON FINAL
2. PLEASE PROVIDE A LETTER OF PERMISSION FROM TRANE TO ALLOW UP TO 30' OF CONDENSATE PIPE BEFORE THE TRAP
3. TIE WIRE NOT APPROVED FOR CLAMPING PIPE
4. OK FOR CEILING TILES. LEAVE OUT AROUND EACH FAN COIL
5. ADDRESS SECONDARY DRAIN LOCATIONS
06/13/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE 90 DEGREE ELBOWS ON SECONDARY DRAINS
2) PROVIDE A MIN 100 PSI HYDROSTATIC TEST ON ALL HYDRONIC PIPING
3) SUSPENDED ROUGH OK TO PROCEED WITH CEILING GRID