Permit: T07CM02157

Parcel: 11011181B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/15/2007 ELECTRIC - FINAL Approved PER INSP CARD PER RMAJUTA 08/14/07
08/13/2007 ELECTRIC - FINAL Denied FOLLOW UP -- LISTING SERIAL #5 9434-306-01
9434-306-02
9434-306-03
9434-306-04
9434-306-05
9434-306-06

WILL NOTIFY UL BEN BAILON, AREA MANAGER
SOUTH WEST SECTION AFTER NOTIFICATION & CALL
AND CONVERSATION WITH MR. BAILON OF UL, DETERMINED A FIELD INSPECTION BY UL NOT REQUIRED, UL TO HANDLE SITUATION WITH HOSPITAL SYSTEMS.
08/10/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) NO FURTHER INSPECTIONS UNTIL UL COMPLETES WORK
08/09/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO INSPECTION UNTIL UL FILES REPORT
08/08/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. UL FIELD LABEL NOT ALLOWED TO BE FIELD INSTALLED BY OTHER THAN UL FIELD PERSONNEL
2. OTHER ITEMS COMPLETED
07/31/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
FINISH PREVIOUS INSPECTION REPORT
NO ONE PRESENT - NO MESSAGE
07/30/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED
07/27/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. MAX DISCONNECT SWITCH HEIGHT 6'7"
2. DRYWALL TO BE WITHIN 1/8" OF AROUND BOX 314.21
3. PLEASE VERIFY LISTING LABEL FOR HOSPITAL SYSTEMS
4. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS 314.20
5. FINISH ELECTRIC FOR SWITCHES
6. NEED ELECTRICIAN PRESENT TO OPEN EQUIPMENT
7. LABEL PANEL AS PER 408.4 -- NO ABBREVIATIONS
8. VERIFY GROUNDING ELECTRODE SYSTEM FOR TRANSFORMER
9. SECURE TRANSFORMER TO STRUCTURE & MAINTAIN CLEARANCES -- 450.9 & 110.26
10. PLEASE PROVIDE INFORMATION ON "CLASSIFIED" DENTAL VACUUM.