Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM02157
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/08/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
07/25/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. FIXTURE MISSING IN RM 306 NORTH END ALSO, J-BOX COVER TO BE PUT ON ABOVE COLUMN OK TO START COVER ON CEILING LEAVE AREAS AROUND #1 OPEN & RECALL |
|
07/23/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PROPERLY SUPPORT VDV CABLING 735.6 & 800.6 NO LAYING ON DUCTS OR STRAPPED TO CONDUITS 2. SUPPORT MC CABLE AS PER CODE 3. ALL FIXTURES TO BE ATTACHED TO GRID 4. IF MC IS SUPPORTED TO FIXTURES IF MUST BE AS PER 300.11 5. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING 250.8 6. CLEAN SURFACE UNDER LUG 7. WHAT IS DISCONNECT ABOVE CEILING CONTROLLING? |