Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T07CM02157

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
08/08/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
07/25/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. FIXTURE MISSING IN RM 306 NORTH END
ALSO, J-BOX COVER TO BE PUT ON ABOVE COLUMN

OK TO START COVER ON CEILING
LEAVE AREAS AROUND #1 OPEN & RECALL
07/23/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PROPERLY SUPPORT VDV CABLING 735.6 & 800.6
NO LAYING ON DUCTS OR STRAPPED TO CONDUITS
2. SUPPORT MC CABLE AS PER CODE
3. ALL FIXTURES TO BE ATTACHED TO GRID
4. IF MC IS SUPPORTED TO FIXTURES IF MUST BE
AS PER 300.11
5. SHEETMETAL SCREWS NOT ALLOWED FOR
GROUNDING 250.8
6. CLEAN SURFACE UNDER LUG
7. WHAT IS DISCONNECT ABOVE CEILING CONTROLLING?