Permit: T07CM02157

Parcel: 11011181B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM02157

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/08/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/20/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK HEAD WALLS & WALL ROOM 309 & 306
1. WALL SUBJECT TO REFERENCE TO MC CABLE
06/13/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALL ROOMS 301-310
06/11/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT CONDUIT WITHIN 3' OF BOXES - NOT TO BE SUPPORTED BY OTHER CONDUITS
2. TIGHTEN LOOSE FITTINGS
3. VERIFY IF FIRE STOPPING IS NEEDED BETWEEN FLOORS
4. PROTECT M/C & FLEX CONDUIT AT SHALLOW STUDS
5. NO MORE THAN 360 DEG. IN A CONDUIT RUN
6. IF MORE THAN 300V BETWEEN DEVICES IS PRESENT A MANUFACTURES SEPARATION DIVIDER IS NEEDED.
7. SPEC'S CALL FOR MINIMUM 3/4" CONDUIT
8. M/C CABLE PROHIBITED PER 2.07 OF SPEC
9. PROVIDE PLASTIC BUSHING ON CONDUIT FOR VDV CABELING AS PER PLANS.