Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM02157
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/08/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
06/20/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK HEAD WALLS & WALL ROOM 309 & 306 1. WALL SUBJECT TO REFERENCE TO MC CABLE |
|
06/13/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALL ROOMS 301-310 |
|
06/11/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT CONDUIT WITHIN 3' OF BOXES - NOT TO BE SUPPORTED BY OTHER CONDUITS 2. TIGHTEN LOOSE FITTINGS 3. VERIFY IF FIRE STOPPING IS NEEDED BETWEEN FLOORS 4. PROTECT M/C & FLEX CONDUIT AT SHALLOW STUDS 5. NO MORE THAN 360 DEG. IN A CONDUIT RUN 6. IF MORE THAN 300V BETWEEN DEVICES IS PRESENT A MANUFACTURES SEPARATION DIVIDER IS NEEDED. 7. SPEC'S CALL FOR MINIMUM 3/4" CONDUIT 8. M/C CABLE PROHIBITED PER 2.07 OF SPEC 9. PROVIDE PLASTIC BUSHING ON CONDUIT FOR VDV CABELING AS PER PLANS. |