Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/29/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/28/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL PROPER SIZE GROUND TO BE #8 FROM JUNCTION BOX TO FIRST DISCONNECT 2. INSTALL #10 GROUND TO AC DISCONNECTS AND UNITS 3. INSTALL BONDING SCREWS IN AC DISCONNECTS 4. BOND JUNCTION BOX WITH #8 |
|
| 03/27/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. LABEL DISCONNECTING MEANS 2. ONLY ONE CONDUCTOR PER TERMINAL LUG 3. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING 4. CONDUCTOR TO BE SIZED PER 240.21 5. BOX OVERFILLED 6. USE CORRECT SIZED WIRE NUTS PER LISTING 7. CANNOT CUT HOLE INSIDE OF CAST BOX 8. USE APPROVED HARDWARE FOR BOXES AND ATTACH TO STRUCTURE 9. BOND DISCONNECT ENCLOSURES 10. CANNOT PASS THRU DISCONNECT 11. TIGHTEN LOOSE FITTINGS 12. IDENTIFY CIRCUIT PHASE CONDUCTORS 13. MAINTENANCE RECEPTACLE IS NEEDED 210.63 |
|
| 11/02/2007 | ELECTRIC - FINAL | Denied | NO PLANS/PERMIT BLD LOCKED |