Permit: T07CM02151

Parcel: 12702232C


Addresses:

5120 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/29/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/28/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL PROPER SIZE GROUND TO BE #8 FROM JUNCTION BOX TO FIRST DISCONNECT
2. INSTALL #10 GROUND TO AC DISCONNECTS AND UNITS
3. INSTALL BONDING SCREWS IN AC DISCONNECTS
4. BOND JUNCTION BOX WITH #8
03/27/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. LABEL DISCONNECTING MEANS
2. ONLY ONE CONDUCTOR PER TERMINAL LUG
3. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING
4. CONDUCTOR TO BE SIZED PER 240.21
5. BOX OVERFILLED
6. USE CORRECT SIZED WIRE NUTS PER LISTING
7. CANNOT CUT HOLE INSIDE OF CAST BOX
8. USE APPROVED HARDWARE FOR BOXES AND ATTACH TO STRUCTURE
9. BOND DISCONNECT ENCLOSURES
10. CANNOT PASS THRU DISCONNECT
11. TIGHTEN LOOSE FITTINGS
12. IDENTIFY CIRCUIT PHASE CONDUCTORS
13. MAINTENANCE RECEPTACLE IS NEEDED 210.63
11/02/2007 ELECTRIC - FINAL Denied NO PLANS/PERMIT BLD LOCKED