Permit: T07CM02144

Parcel: 14118001H


Addresses:

8290 S HOUGHTON RD


Inspection Status: Approved

Inspection History: ELECTRIC - PROGRESS

Permit Number - T07CM02144

Inspection Description - ELECTRIC - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
11/20/2007 ELECTRIC - PROGRESS Approved IVRS - Inspection :*
10/31/2007 ELECTRIC - PROGRESS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE LETTER OF TORQUE FOR TERMINATIONS IN NEW SWITCHGEAR
2. PROVIDE BELL ENDS FOR PROTECTION OF SERVICE CONDUCTORS AT PVC ENTRANCE INTO BOTTOM OF SWITCHGEAR -- NEC 352.46
3. SERVICE CONDUCTORS NOT SIZED PER APPROVED PLANS
4. PROVIDE APPROVED APPEAL NOTICE