Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/20/2007 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* | |
| 10/31/2007 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE LETTER OF TORQUE FOR TERMINATIONS IN NEW SWITCHGEAR 2. PROVIDE BELL ENDS FOR PROTECTION OF SERVICE CONDUCTORS AT PVC ENTRANCE INTO BOTTOM OF SWITCHGEAR -- NEC 352.46 3. SERVICE CONDUCTORS NOT SIZED PER APPROVED PLANS 4. PROVIDE APPROVED APPEAL NOTICE |