Permit: T07CM02144

Parcel: 14118001H


Addresses:

8290 S HOUGHTON RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM02144

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/20/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/25/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. OK 3 - 4" PVC FROM TEP XFMR TO SES
2. WHAT SIZE SERVICE ENTRANCE CONDUCTORS ARE GOING TO BE INSTALLED?
3. GROUNDING ON PLANS CALLS FOR 350 MCM CU
4. WHY ARE WE ADDING 2ND SERVICE TO BUILDING INSTEAD OF UPGRADING EXISTING TO MEET NEW DEMAND. I BELIEVE THAT 230.2 DOES NOT ALLOW THIS TYPE OF INSTALLATION
SECTION 230.40 EXCEPTION #2 MAY ALLOW THIS TYPE OF INSTALLATION BUT THE ENCLOSURES ARE REQUIRED TO BE GROUPED. SEE ALSO NEC 230.72 THE TWO ENCLOSURES WILL BE APPROX 30' APART & IN MY OPINION IS NOT GROUPED.
5. GROUNDING ELECTRODE CONDUCTOR INSTALLED IN METAL RACEWAY TO BE BONDED AT BOTH ENDS OF RACEWAY
NEC 250.64 (E)
09/05/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS X-RAY R102