Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM02144
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/20/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
09/25/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. OK 3 - 4" PVC FROM TEP XFMR TO SES 2. WHAT SIZE SERVICE ENTRANCE CONDUCTORS ARE GOING TO BE INSTALLED? 3. GROUNDING ON PLANS CALLS FOR 350 MCM CU 4. WHY ARE WE ADDING 2ND SERVICE TO BUILDING INSTEAD OF UPGRADING EXISTING TO MEET NEW DEMAND. I BELIEVE THAT 230.2 DOES NOT ALLOW THIS TYPE OF INSTALLATION SECTION 230.40 EXCEPTION #2 MAY ALLOW THIS TYPE OF INSTALLATION BUT THE ENCLOSURES ARE REQUIRED TO BE GROUPED. SEE ALSO NEC 230.72 THE TWO ENCLOSURES WILL BE APPROX 30' APART & IN MY OPINION IS NOT GROUPED. 5. GROUNDING ELECTRODE CONDUCTOR INSTALLED IN METAL RACEWAY TO BE BONDED AT BOTH ENDS OF RACEWAY NEC 250.64 (E) |
|
09/05/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS X-RAY R102 |