Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T07CM02143
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/08/2007 | FRAMING | Approved | IVRS - Inspection :* | |
06/05/2007 | FRAMING | Not ready for Inspection | IVRS - Inspection :* | |
05/31/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
05/24/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LAG BOLTS REQUIRED 1" WASHERS 2) SCREWS NOT ALLOWED IN H2.5-USE TECO NAILS ALSO AT POSTS 3) LEDGER LAGS REQUIRED AT STUDS LOCATED AT 16" ON CENTER 4) LEDGER ? METAL NOT INSTALLED 5) PLAN CALLS FOR 3 1/8 X 13 1/2 GLUE LAM BEAM BUILT UP DBL 2 X 12 IS NOT EQUAL-BUILD TO PLAN 6) PORCH CONCRETE TO STAND OFF IS POURED WITH COLD JOINT-PROVIDE PROOF THAT ANCHOR BOLT EXTENDS AT LEAST 2 1/2" INTO SLAB |