Permit: T07CM02143

Parcel: 141095570


Addresses:

6426 E STAR MICA ST


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T07CM02143

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
06/08/2007 FRAMING Approved IVRS - Inspection :*
06/05/2007 FRAMING Not ready for Inspection IVRS - Inspection :*
05/31/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/24/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LAG BOLTS REQUIRED 1" WASHERS
2) SCREWS NOT ALLOWED IN H2.5-USE TECO NAILS ALSO AT POSTS
3) LEDGER LAGS REQUIRED AT STUDS LOCATED AT 16" ON CENTER
4) LEDGER ? METAL NOT INSTALLED
5) PLAN CALLS FOR 3 1/8 X 13 1/2 GLUE LAM BEAM BUILT UP DBL 2 X 12 IS NOT EQUAL-BUILD TO PLAN
6) PORCH CONCRETE TO STAND OFF IS POURED WITH COLD JOINT-PROVIDE PROOF THAT ANCHOR BOLT EXTENDS AT LEAST 2 1/2" INTO SLAB