Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/19/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 10/17/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* HORIZ. UNIT IN ATTIC NOT LEVEL CAUSING WATER TO RUN OUT OF PAN INTO DUCT WORK. 1. RE-LEVEL UNIT 2. REPLACE ALL WET INSULATION AT SUPPLY DUCT 3. FLUE PIPE TOO CLOSE TO COMBUSTIBLE MATERIAL AT ROOF LINE 4. PRIMER WAS NOT USED ON ALL PVC CONDENSATE JOINTS SOME JOINTS NO GLUE. REPAIR CONDENSATE PIPING USING PRIMER AND GLUE APPROVED FOR PVC PIPE ON ALL JOINTS. |