Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/03/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* OK TO COVER ALL AREAS |
|
| 10/02/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* REC'D LETTER ALLOWING PEX |
|
| 10/01/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. CONTRACTOR TO HAVE MATERIAL CHANGE FOR YARDWATER ADDED TO LETTER 2. CONTRACTOR TO ADD HANGERS OVERHEAD AS REQUIRED 3. WATER TEST OK ON DWV 4. PRESSURE TEST FOR PEX OK 5. TUBS OK OK TO COVER ALL AREAS |
|
| 09/28/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) PVC YARDWATER NOT OK TO COVER WITH CLEANFILL 2) PLAN CALLS FOR TYPE "L" COPPER INSTALLED IS PEX 3) PEX PLAN CALLS FOR SCHEDULE 40 PVC-INSTALLED IS PEX 4) ABS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES THEN NO MORE THAN FOUR FEET BETWEEN HANGERS 5) VENTS BELOW FLOOD RIM TO BE DRAINAGE FITTING 6) HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP 7) NEED TO SEE FLANGES 8) NO TEST ON ABS 9) SUPPORT VERTICAL PIPING |