Permit: T07CM02094

Parcel: 141315890

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T07CM02094

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
08/02/2007 FRAMING Approved IVRS - Inspection :*
07/30/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONDUIT AT KIT ISLAND, TO BE INSTALLED IN A MANNER SO AS ROMEX CAN BE FED, WITHOUT REMOVING CONCRETE OR FLOORING
2) 12" PEX TO CAN LIGHT BOT. OF STAIR, KIT ISLAND
3) FHA STRAPS AT 2 X 6 STUD, HOLE 3" ABS LAUNDRY
4) STUD CUT AT STAIR ? LIGHT
5) CHOOSE ATTIC ACCESS, REMOVE OBSTRUCTION
6) TUB SURROUND BACKING BOTH 2ND FLOOR, OVER NOTCHED DIVERTER STUD
7) CONDENSATES NOT COMPLETE CHECK FOR NAIL HOLES WEST WALL VERT. CONDENSATE
8) FAN EXHAUST 2ND FLOOR TOILET ROMEX NOT CONNECTED