Permit: T07CM02091

Parcel: 137053210


Addresses:

701 W WYOMING ST

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
11/28/2007 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
10/04/2007 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SERVICE OK BUT YOUR PLAN CALLS FOR UNDERGROUND ELECTRIC SERVICE. YOU MUST OBTAIN A WAIVER FROM CITY OF TUCSON TO USE AN OVERHEAD ELECTRIC SERVICE
10/02/2007 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
PER D WITT:
1) USE HTT22 HD'S EAST SIDE GARAGE WITH EPOXY BOLTS
2) PA STRAPS WEST SIDE GARAGE OK
3) HOUSE FULLY SHEARED SO REMAINING PA STRAPS NOT REQUIRED
4) OK TO DRY IN AND WRAP
5) UFER MUST BE CAD WELDED OR USE AN APPROVED NON REVERSEIBLE COUPLING