Permit: T07CM02085

Parcel: 119421470

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
10/08/2007 BUILDING - FINAL Approved IVRS - Inspection :*
10/04/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REMOVE UNUSED TILE FROM ROOF-FALLING HAZARD
2) DBL LUGGING OF CIRCUIT BREAKER 24 NOT ALLOWED
3) KITCHEN COUNTER MUST HAVE TWO SEPERATE 20 AMP CIRCUITS-ONLY ONE LABELED IN PANEL
4) SEAL FURNACE AND W/H SINGLE WALL JOINTS WITH APPROVED ?
5) SEAL GARAGE WALL PENETRATIONS AT GAS LINES
6) ELECTRIC PANEL CIRCUITS NOT PROPERLY LABELED