Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T07CM02064
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/20/2007 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 08/15/2007 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) STILL HAVE 2 TRUSS ISSUES 2) QUEST PLEASE LEAVE TRUSS DRAWINGS TO COMPARE WITH REPAIR-REPAIR SHOWS 2 X 4 END TO END ? |
|
| 08/08/2007 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) OK TO COVER 2) STILL HAVE 2 TRUSS ISSUES |
|
| 08/06/2007 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MISSING GUSSET PLATE END TRUSS WEST 2. TWO E1A TRUSSES NOTCHED AT HANGERS 3. 3-2X6 TRIMMERS AT MSTR. BED. DRL 2X10 HEADER 4. MISSED NAILING ABOVE KIT. ROOF (MARKED IN BLACK) 5. BLK. UNDER FRONT ENTRA. ROOF AT BOT. PLATE 6. AT FLR. TRUSS OVERSPAN NAIL 2X5 TOGETHER 7. MISSING WIND BRACE 2ND FLOOR REAR |