Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM02057
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/06/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
05/30/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
05/21/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. REATTACH NURSE CALL TO CEILING AND SUPPORT CABLING 2. SUPPORT WIRE NEEDED FOR EXIT SIGN 3. FINISH SUPPORTING OTHER VDV CABLING 4. MISSING CAN JUNCTION BOX COVER (OLD) |
|
04/03/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* FINISH VDV 300 AREA LOBBY OK PATIENT ROOMS |
|
04/02/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CANNOT USE FLEX FOR CHAIR LIGHTS CITY AMENDMENT TO NOT ALLOW FLEX TO MEET REQUIREMENTS OF 250.118 WIRE METHOD TO BE AS PER 517.13 2. FINISH PREVIOUS #2 |
|
03/28/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. FINISH CHAIR LIGHTS 2. SUPPORT WIRE TO BE ATTACHED BOTH ENDS 300.11 |
|
03/21/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK ROOMS 201, 204-227, 231, 232, 306 FINISH ELECTRIC |
|
03/20/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* FINISH #3 & #4 OF PREVIOUS INSPECTIONS |
|
03/19/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
03/18/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. SECURE FIXTURES TO GRID 410.16 MANUFACTURE CLIPS TO BE EFFECTIVE 2. SUPPORT EXIT SIGNS WITH SUPPORT WIRES 3. SUPPORT VDV CABLING 700.6, 800.6, 300.11 - CANNOT USE CONDUIT AS SUPPORT 4. FINISH BOX MAKE UP 5. BOX OVERFILLED 6. FINISH CHAIR LIGHTS |
|
03/03/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* SUPPORT MC WITHIN 12" OF BOXES FROM STRUCTURE OK TO TILE ROOM 202 AFTER CORRECTIONS |
|
12/19/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK HARD LIDS INTERIOR |