Permit: T07CM02057

Parcel: 110072620


Addresses:

2732 N ALVERNON WY

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
06/06/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
05/30/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
05/21/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. REATTACH NURSE CALL TO CEILING AND SUPPORT CABLING
2. SUPPORT WIRE NEEDED FOR EXIT SIGN
3. FINISH SUPPORTING OTHER VDV CABLING
4. MISSING CAN JUNCTION BOX COVER (OLD)
04/03/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
FINISH VDV 300 AREA LOBBY
OK PATIENT ROOMS
04/02/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CANNOT USE FLEX FOR CHAIR LIGHTS CITY AMENDMENT TO NOT ALLOW FLEX TO MEET REQUIREMENTS OF 250.118 WIRE METHOD TO BE AS PER 517.13
2. FINISH PREVIOUS #2
03/28/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. FINISH CHAIR LIGHTS
2. SUPPORT WIRE TO BE ATTACHED BOTH ENDS 300.11
03/21/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK ROOMS 201, 204-227, 231, 232, 306

FINISH ELECTRIC
03/20/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
FINISH #3 & #4 OF PREVIOUS INSPECTIONS
03/19/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
03/18/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. SECURE FIXTURES TO GRID 410.16 MANUFACTURE CLIPS TO BE EFFECTIVE
2. SUPPORT EXIT SIGNS WITH SUPPORT WIRES
3. SUPPORT VDV CABLING 700.6, 800.6, 300.11 - CANNOT USE CONDUIT AS SUPPORT
4. FINISH BOX MAKE UP
5. BOX OVERFILLED
6. FINISH CHAIR LIGHTS
03/03/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
SUPPORT MC WITHIN 12" OF BOXES FROM STRUCTURE

OK TO TILE ROOM 202 AFTER CORRECTIONS
12/19/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK HARD LIDS INTERIOR