Inspection History Details
Permit: T07CM02039
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 11/13/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CAULK SINKS AND INSTALL CLIPS 2) ICE DRAIN REDUCED AND NOT PRIMED 3) PRIME PVC 10 WAST PIPING 4) 1 SLIP NUT ON STEM OF TRAP AT SINK 5) SUPPORT MIXING VALVES 6) PROVIDE BACKFLOW PROTECTION FOR NON CARBONATED BEV UP STREAM OF CARBONATOR RP. PROVIDE UNION RP. PROVIDE BACKFLOW CERT 7) LIST MAY NOT BE COMPLETE |
|
| 11/01/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* - WET VENTED HAND SINK (REQUIRED BY HEALTH DEPT.) - ABOVE P-10 OK - OK TO COVER, SUBJECT TO REVISED APPROVED PLAN - ONLY SANITIZER AND VEGETABLE PREP TO GO INDIRECT - OTHER SINKS TO BE DIRECTLY CONNECTED TO SANITARY SEWER - ALL I.W PIPING TO BE APPROVED TYPE, INSTALLED PLUMB, AND SQUARE WITH 1/4" PITCH TO DRAIN |