Permit: T07CM02039
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2007 | PLUMBING - ROUGH, SOIL | Approved | PER PL FINAL | |
| 09/05/2007 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | 1. EXCEPT FOR WYE BRANCH, AND END OF THE LINE CLEANOUTS, CLEANOUTS SHALL BE INSTALLED ABOVE THE FLOW LINE OF THE PIPE. 2. ABS SHALL BE INSTALLED WITH SUPPORT AT EACH CHANGE OF DIRECTION OR ELEVATION, AND AT THE END OF BRANCHES THEN NO MORE THAN FOUR FEET BETWEEN HANGERS. 3. VERTICAL PIPING SHALL BE SUPPORTED AT EACH FLOOR LEVEL WITH MID-STORY GUIDES. 4. WOOD SHIMS NOT APPROVED SUPPORTS 5. PIPING TO BE INSTALLED PARALLEL WITH BUILDING LINES OR AT RIGHT ANGLES THERE TO USING STANDARD INSTALLATION PRACTICES. 6. SEE PLUMBING SPEC. #10 INSULATION 7. INSPECTION STOPPED. |
|