Permit: T07CM02039


Addresses:

4585 N ORACLE RD


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T07CM02039

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
11/15/2007 PLUMBING - ROUGH, SOIL Approved PER PL FINAL
09/05/2007 PLUMBING - ROUGH, SOIL Not ready for Inspection 1. EXCEPT FOR WYE BRANCH, AND END OF THE LINE CLEANOUTS, CLEANOUTS SHALL BE INSTALLED ABOVE THE FLOW LINE OF THE PIPE.
2. ABS SHALL BE INSTALLED WITH SUPPORT AT EACH CHANGE OF DIRECTION OR ELEVATION, AND AT THE END OF BRANCHES THEN NO MORE THAN FOUR FEET BETWEEN HANGERS.
3. VERTICAL PIPING SHALL BE SUPPORTED AT EACH FLOOR LEVEL WITH MID-STORY GUIDES.
4. WOOD SHIMS NOT APPROVED SUPPORTS
5. PIPING TO BE INSTALLED PARALLEL WITH BUILDING LINES OR AT RIGHT ANGLES THERE TO USING STANDARD INSTALLATION PRACTICES.
6. SEE PLUMBING SPEC. #10 INSULATION
7. INSPECTION STOPPED.
08/02/2007 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
1. WILL REQUIRE LETTER ALLOWING SCH 40 ABS
OK TO COVER SANITARY SEWER
OK TO COVER GREASE WASTE
2. CALL FOR PRE-SLAB