Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM02039
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/14/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
11/13/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) IDENTIFY ALL DISCONNECTS 2) PANEL DIRECTORYS TO CORRECT, NUMBER BREAKERS 3) MISSING TWO EMERGENCY FIXTURES 4) GROUNDS #6 AND SMALLER TO BE GREEN, PROPERLY IDENTIFY ALL EQUIPMENT GROUNDS |
|
11/07/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
11/06/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* PARTIAL INSPECTION FOR INTERIOR WORK IN PROGRESS @ HOOD AREA EQUIPMENT/STOCK TO BE OUT OF WAY FOR INSPECTION EMERGENCY LIGHTING TO BE AIMED SO IT IS EFFECTIVE |
|
11/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR ROOFTOP 1. SATELLITE DISH TO BE PROPERLY GROUNDED AND COAX RAN IN A NEAT MANNER SO AS NOT TO BE A TRIPPING HAZARD 2. IDENTIFY ALL ROOFTOP EQUIPMENT AND DISCONNECTS 3. DISCONNECTS TO HAVE MINIMUM 36" FRONT WORKING CLEARANCE 4. WALK IN CONDENSOR OVERFUSED (WEST UNIT) 5. ROOFTOP GFI BY CONDENSORS SHOWS OPEN NEUTRAL 6. NEED K.O SEAL RTU 3 DISCONNECT 7. STRAP ALL FLEX WITHIN 12" OF TERMINATION, TIGHTEN ALL FITTINGS 8. DATA PLATES TO BE CORRECTLY IDENTIFIED ON RTU'S FUSE ACCORDINGLY 9. SEAL UNUSED RACEWAYS THROUGH ROOF 10. REMOVE L.V WIRE STRETCHED LENGTH OF ROOF 11. IDENTIFY PANEL DIRECTORY AT SERVICE (CLEAR, CORRECT AND LEGIBLE) 12. PVC TO HAVE PROTECTIVE BUSHING FOR CUT END 13. WIRING/EQUIPMENT TO BE PER PLAN - PLANS CALL FOR NEW RTU'S (2) |
|
11/01/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CALLED IN BEFORE COMPLETE |
|
10/31/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED |