Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM02039
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/14/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
10/10/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING TILES |
|
10/09/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION ABOVE WALK IN'S 1. SECURE FLEX WITHIN 12" OF TERMINATIONS 2. HAVE OVERFILLED BOXES 3. SEAL RACEWAYS INTO WALK IN'S 4. RACEWAYS TO BE RAN IN A NEAT AND WORKMAN LIKE MANNER FOLLOW BUILDING SURFACE. 5. FF#2 J-BOX & WIRING NOT COMPLETE, VERIFY PROPER CKT SIZE (7.2 KW & 2 AMP MOTOR @ 208) NEED PROPER GROUND (SIZE), LOW VOLTAGE (STAT) NOT ALLOWED IN SAME RACEWAY ENCLOSURE AS POWER OK CEILING TILES FROM EAST TO SERVICE COUNTER |
|
10/08/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
10/05/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HAVE OVERFILLED J-BOXES (NEC 314.16) 2. HAVE EXPOSED HOT CONDUCTOR @ WIRE NUTS (STRIP TO FAR) NEC 110.3 B 3. FINISH ALL WIRING AND DEMO ABOVE CEILING 4. NEED BUSHING #4 & LARGER WIRE |