Permit: T07CM02039


Addresses:

4585 N ORACLE RD

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
11/14/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
10/10/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING TILES
10/09/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION

ABOVE WALK IN'S
1. SECURE FLEX WITHIN 12" OF TERMINATIONS
2. HAVE OVERFILLED BOXES
3. SEAL RACEWAYS INTO WALK IN'S
4. RACEWAYS TO BE RAN IN A NEAT AND WORKMAN LIKE MANNER FOLLOW BUILDING SURFACE.
5. FF#2 J-BOX & WIRING NOT COMPLETE, VERIFY PROPER CKT SIZE (7.2 KW & 2 AMP MOTOR @ 208) NEED PROPER GROUND (SIZE), LOW VOLTAGE (STAT) NOT ALLOWED IN SAME RACEWAY ENCLOSURE AS POWER

OK CEILING TILES FROM EAST TO SERVICE COUNTER
10/08/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
10/05/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HAVE OVERFILLED J-BOXES (NEC 314.16)
2. HAVE EXPOSED HOT CONDUCTOR @ WIRE NUTS
(STRIP TO FAR) NEC 110.3 B
3. FINISH ALL WIRING AND DEMO ABOVE CEILING
4. NEED BUSHING #4 & LARGER WIRE