Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM02039
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/14/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
09/06/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK REMAINDER INTERIOR WALL COVER NOTE: GFI PROTECTION REQUIRED FOR ALL 120V CONSTRUCTION RECEPTACLES - CORRECT BEFORE THESE RECEPTACLES ARE USED. |
|
09/04/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE NAIL PLATE PROTECTION FOR MC & PVC - NEC 300 2. MC TO BE SECURED WITHIN 12" OF TERMINATIONS - NEC 330 USE PROPERLY SIZED STRAPS 3. SECURE FLEX IN WALL 4. EMT TO BE SECURED WITHIN 36" OF ENCLOSURES 5. SEAL UNUSED OPENINGS. |
|
08/31/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL COVER ENTRY AREA FIRE RISER ROOM (PER PLAN) AND INTERIOR AREAS EAST OF THAT ROOM |
|
08/07/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK INTERIOR UNDER SLAB RACEWAYS (PVC) |
|
08/06/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : 1. WORK NOT COMPLETE 2. NO PLANS ON SITE |