Permit: T07CM02039


Addresses:

4585 N ORACLE RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
11/14/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/06/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK REMAINDER INTERIOR WALL COVER

NOTE: GFI PROTECTION REQUIRED FOR ALL 120V CONSTRUCTION RECEPTACLES - CORRECT BEFORE THESE RECEPTACLES ARE USED.
09/04/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE NAIL PLATE PROTECTION FOR MC & PVC - NEC 300
2. MC TO BE SECURED WITHIN 12" OF TERMINATIONS - NEC 330
USE PROPERLY SIZED STRAPS
3. SECURE FLEX IN WALL
4. EMT TO BE SECURED WITHIN 36" OF ENCLOSURES
5. SEAL UNUSED OPENINGS.
08/31/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL COVER ENTRY AREA FIRE RISER ROOM (PER PLAN)
AND INTERIOR AREAS EAST OF THAT ROOM
08/07/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK INTERIOR UNDER SLAB RACEWAYS (PVC)
08/06/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
1. WORK NOT COMPLETE
2. NO PLANS ON SITE