Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM02035
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/23/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/29/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH #5 PREVIOUS INSPECTION OTHER ITEMS CORRECTED |
|
04/17/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. INSTALL CONDUCTORS IN APPROVED RACEWAYS & SUPPORT 2. WHERE ARE RECEPTACLES ON SOUTH WALL 3. LABEL EQUIPMENT AND BLOWERS 4. FINISH CABLE TRAY GROUNDING 392.7 5. SECURE CABLES PER 312.52(C) & 314.17(B) 6. CONDUCTOR TO ENTER SECTION SERVED 408.3 7. FILL UNUSED OPENINGS *RECEIVED COPY OF UL FIELD EVALUATION |