Permit: T07CM02035

Parcel: 140420530


Addresses:

2207 E ELVIRA RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/23/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/29/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FINISH #5 PREVIOUS INSPECTION

OTHER ITEMS CORRECTED
04/17/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. INSTALL CONDUCTORS IN APPROVED RACEWAYS & SUPPORT
2. WHERE ARE RECEPTACLES ON SOUTH WALL
3. LABEL EQUIPMENT AND BLOWERS
4. FINISH CABLE TRAY GROUNDING 392.7
5. SECURE CABLES PER 312.52(C) & 314.17(B)
6. CONDUCTOR TO ENTER SECTION SERVED 408.3
7. FILL UNUSED OPENINGS

*RECEIVED COPY OF UL FIELD EVALUATION