Permit: T07CM02035

Parcel: 140420530


Addresses:

2207 E ELVIRA RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM02035

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/23/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/29/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/17/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
02/11/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK NORTH EXT. WALL ROUGH - OK TO ROCK SUBJECT
TO FRAMING APPROVAL
02/02/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
CONTR. NOT ON SITE, RECALL INSPECTION
LEAVE MESSAGE, HAVE ELEC. CONTR. ON SITE
10/14/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK GROUNDING BLD, STEEL, WATER
2. SEE NOTES PREVIOUS INSPECTIONS FOR NRTL LISTING OF EQUIP.
10/03/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
10/02/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. VERIFY GROUNDING ELECTRODE SYSTEM FOR EXISTING BLDG.'s
2. REVISED PLANS TO INDICATE METHOD TO RE-FEED EXISTING S.W GEAR
3. LARGE EQUIP. SUCH AS HEATING EQUIP., CONTROL CABINET AND BLOWER CONTROL CAB. FAN BLOWERS DO NOT HAVE NRTL LISTING OR LABELING. WILL REQUIRE 3RD PARTY EVALUATION.
09/30/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. REVISED PLANS NEED TO BE STAMPED THRU PLAN CHECK
2. RECEIVED LETTER OR GFI MAIN BREAKER TEST RESULTS
09/26/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
CONTR. NOT ON SITE - NO MESSAGE
RECALL INSPECTION
09/11/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. LABEL BREAKERS
2. PROVIDE COPIES OF GFI BREAKER TEST AS REQUIRED
PER 230.95 NEC
3. BOND BLD. STEEL, WATER, GAS, PIPING PER 250.104 NEC
4. RECEIVED LETTER OF TORQUE
5. FEEDERS TO FANS DO NOT MEET NEC REQUIREMENTS
PER 310.11
6. REVISED PLANS NEED TO BE STAMPED THRU PLAN CHECK
09/03/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROVIDE BUSHED ENDS ON CONDUIT ENTRIES INTO SES & OTHER GEAR PER 300.5H, 300.15C, 300.16B, 352.46 NEC
2. PROVIDE REVISED PLAN FOR INSTALLATIONS OF ALL ELECTRICAL EQUIP.
3. COMPLETE ALL GROUNDING AND BONDING
4. PROVIDE LETTER OF TORQUE FOR SES AND EQUIP.
5. PROVIDE GFI MAIN BREAKER TESTING PER 230.95 NEC
PER MANUF.
07/10/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK NORTH EXTERIOR WALLS RECEPT. ROUGH
02/26/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK UFER & CONDUIT STUB UPS
02/22/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
U.G COVERED PRIOR TO INSPECTION