Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM02035
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/23/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
05/29/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/17/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
02/11/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK NORTH EXT. WALL ROUGH - OK TO ROCK SUBJECT TO FRAMING APPROVAL |
|
02/02/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* CONTR. NOT ON SITE, RECALL INSPECTION LEAVE MESSAGE, HAVE ELEC. CONTR. ON SITE |
|
10/14/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK GROUNDING BLD, STEEL, WATER 2. SEE NOTES PREVIOUS INSPECTIONS FOR NRTL LISTING OF EQUIP. |
|
10/03/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
10/02/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. VERIFY GROUNDING ELECTRODE SYSTEM FOR EXISTING BLDG.'s 2. REVISED PLANS TO INDICATE METHOD TO RE-FEED EXISTING S.W GEAR 3. LARGE EQUIP. SUCH AS HEATING EQUIP., CONTROL CABINET AND BLOWER CONTROL CAB. FAN BLOWERS DO NOT HAVE NRTL LISTING OR LABELING. WILL REQUIRE 3RD PARTY EVALUATION. |
|
09/30/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. REVISED PLANS NEED TO BE STAMPED THRU PLAN CHECK 2. RECEIVED LETTER OR GFI MAIN BREAKER TEST RESULTS |
|
09/26/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* CONTR. NOT ON SITE - NO MESSAGE RECALL INSPECTION |
|
09/11/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. LABEL BREAKERS 2. PROVIDE COPIES OF GFI BREAKER TEST AS REQUIRED PER 230.95 NEC 3. BOND BLD. STEEL, WATER, GAS, PIPING PER 250.104 NEC 4. RECEIVED LETTER OF TORQUE 5. FEEDERS TO FANS DO NOT MEET NEC REQUIREMENTS PER 310.11 6. REVISED PLANS NEED TO BE STAMPED THRU PLAN CHECK |
|
09/03/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROVIDE BUSHED ENDS ON CONDUIT ENTRIES INTO SES & OTHER GEAR PER 300.5H, 300.15C, 300.16B, 352.46 NEC 2. PROVIDE REVISED PLAN FOR INSTALLATIONS OF ALL ELECTRICAL EQUIP. 3. COMPLETE ALL GROUNDING AND BONDING 4. PROVIDE LETTER OF TORQUE FOR SES AND EQUIP. 5. PROVIDE GFI MAIN BREAKER TESTING PER 230.95 NEC PER MANUF. |
|
07/10/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK NORTH EXTERIOR WALLS RECEPT. ROUGH |
|
02/26/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK UFER & CONDUIT STUB UPS |
|
02/22/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* U.G COVERED PRIOR TO INSPECTION |