Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/16/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/01/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
07/30/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL MAIN BONDING JUMPER AT SERVICE DISCONNECT
NEC 250.28
2. DO NOT RUN EQUIPMENT GROUNDING CONDUCTOR INTO SERVICE WIRE WAY. AVOID PARALLEL NEUTRAL PATHS.
3. INSTALL BONDING JUMPERS ON LINE SIDE OF SERVICE
DISCONNECT PER NEC 250.102
4. INSTALL FUSES
07/06/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK WALLS
2. OK BATHROOM CEILING