Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/16/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/01/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 07/30/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL MAIN BONDING JUMPER AT SERVICE DISCONNECT NEC 250.28 2. DO NOT RUN EQUIPMENT GROUNDING CONDUCTOR INTO SERVICE WIRE WAY. AVOID PARALLEL NEUTRAL PATHS. 3. INSTALL BONDING JUMPERS ON LINE SIDE OF SERVICE DISCONNECT PER NEC 250.102 4. INSTALL FUSES |
|
| 07/06/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK WALLS 2. OK BATHROOM CEILING |