Permit: T07CM02030

Parcel: 133233870


Addresses:

7494 E DEEPS WY


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T07CM02030

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
10/16/2007 FRAMING Approved IVRS - Inspection :*
09/27/2007 FRAMING Partial Approval IVRS - Inspection :*
1) FIRE STOP CHASE
2) OK TO INSULATE
09/25/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FIRE STOP CHASE AT CEILING AND FIREPLACE
2) SMOKIE INTERCONNECT MUST BE IN SAME CASING AS GROUND WIRE
3) LEAK IN ABS UNDER FLOOR
4) SUPPLY TEST OK
09/18/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) STRAIGHTEN FIREBLOCK AT FURNACE
2) BLOCK REGISTER BOOTS
3) NEED AT LEAST 1/4" OUTER INSULATION
4) ADD RECEPTACLE NEAR FIREPLACE
5) SMOKIES NEED TO BE INTER CONNECTED
6) NO DWV OR SUPPLY TEST
7) PEX NEEDS 12" CLEAR TO CAN LIGHTS
8) SUPPORT ABS EVERY 4'
9) FIRE STOP B-VENTS AND DUCTS AT FLOORS AND CEILING
10) INSTALL STUCCO MESH