Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T07CM02030
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/16/2007 | FRAMING | Approved | IVRS - Inspection :* | |
09/27/2007 | FRAMING | Partial Approval | IVRS - Inspection :* 1) FIRE STOP CHASE 2) OK TO INSULATE |
|
09/25/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FIRE STOP CHASE AT CEILING AND FIREPLACE 2) SMOKIE INTERCONNECT MUST BE IN SAME CASING AS GROUND WIRE 3) LEAK IN ABS UNDER FLOOR 4) SUPPLY TEST OK |
|
09/18/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) STRAIGHTEN FIREBLOCK AT FURNACE 2) BLOCK REGISTER BOOTS 3) NEED AT LEAST 1/4" OUTER INSULATION 4) ADD RECEPTACLE NEAR FIREPLACE 5) SMOKIES NEED TO BE INTER CONNECTED 6) NO DWV OR SUPPLY TEST 7) PEX NEEDS 12" CLEAR TO CAN LIGHTS 8) SUPPORT ABS EVERY 4' 9) FIRE STOP B-VENTS AND DUCTS AT FLOORS AND CEILING 10) INSTALL STUCCO MESH |