Permit: T07CM02004

Parcel: 141350050

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T07CM02004

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
07/11/2007 FRAMING Approved IVRS - Inspection :*
07/10/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MINIMUM 3-10D NAILS AT ENDS OF BLOCKING THROUGH BOTTOM CHORD WITH 4-10D
2) NAILS DOWN INTO SHEARWALL TOP PLATE PER 502 ON INTERIOR SHEARWALLS
3) FILL ALL HOLES IN FHA STRAPS WITH 16D NAILS AT TOP PLATE OVER A/C LINE
4) NAIL PROTECTION NEEDED UNDER WINDOWS IN KITCHEN AND BACK BEDROOM
5) NO PRESSURE ON POTABLE WATER LINES