Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/14/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/31/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OR ROUGH FINAL APPROVAL SUBJECT TO APPROVED REVISION |
|
| 07/20/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED REVISION TO PLANS SHOWING ALL NEW WORK AND NEEDS TO BE APPROVED BY DOWNTOWN 2. TYPE NM CABLE CANNOT BE EMBEDDED IN PLASTER NEC 314.12 (10) 3. WIRING INSTALLED IN SHALLOW GROOVES TO BE PROTECTED PER NEC 300.4(E) 4. INSTALL SEALS IN OPEN KNOCKOUTS - NEC 110.12 5. PROPERLY GROUND ALL METAL BOXES -- NEC 314.4 6. HOW ARE METAL MUD RINGS ON PLASTIC BOXES TO BE GROUNDED? 7. CHECK ALL MUD RINGS TIGHTENED 8. NEED MIN. 6" OF FEE CONDUCTOR LENGTH - NEC 300.14 9. PROPERLY TWIST GROUNDS TOGETHER & INSTALL BARRELL CRIMPS WITH PROPER CRIMP TOOL. |