Permit: T07CM02002

Parcel: 12216233A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/14/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/31/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OR ROUGH FINAL APPROVAL SUBJECT TO APPROVED REVISION
07/20/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED REVISION TO PLANS SHOWING ALL NEW WORK AND NEEDS TO BE APPROVED BY DOWNTOWN
2. TYPE NM CABLE CANNOT BE EMBEDDED IN PLASTER
NEC 314.12 (10)
3. WIRING INSTALLED IN SHALLOW GROOVES TO BE PROTECTED PER NEC 300.4(E)
4. INSTALL SEALS IN OPEN KNOCKOUTS - NEC 110.12
5. PROPERLY GROUND ALL METAL BOXES -- NEC 314.4
6. HOW ARE METAL MUD RINGS ON PLASTIC BOXES TO BE GROUNDED?
7. CHECK ALL MUD RINGS TIGHTENED
8. NEED MIN. 6" OF FEE CONDUCTOR LENGTH - NEC 300.14
9. PROPERLY TWIST GROUNDS TOGETHER & INSTALL BARRELL CRIMPS WITH PROPER CRIMP TOOL.