Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/13/2009 | ELECTRIC - ABOVE CEILING | Approved | ||
| 03/04/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 03/02/2009 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* EXIT J-BOXES K-O SEAL MISSING 3/4 J-BOX CIRCUIT 5 HAS K-O SEAL MISSING 3/4 REMOVE OR PUT BOX ON SPARE 3/4 1. NEED TO CHANGE BREAKERS FROM 10,000 22,000 2. LOW VOLTAGE PIPE NEEDS PLASTIC BUSHING |