Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2007 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 10/30/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO CORRECTIONS FROM PRIOR INSPECTION 2) HOUSE LOCKED |
|
| 09/28/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ELECTRIC PANEL DEAD FRONT MISSING MOUNTING SCREW 2) CIRCUIT 22 HAS 14 GAUGE WIRE 20 AMP BREAKER MAX ALLOWED 15 AMP BREAKER 3) CIRCUIT 22 NOT GROUNDED 4) IRRIGATION TIMER WIRES NOT PROPERLY CONNECTED 5) DEN REQUIRES SWITCHED LIGHT SOURCE 6) EXPOSE ISLAND BOX CABLE CONNECTION AT END OPPOSITE OUTLET |
|
| 09/17/2007 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NOT READY PER SUPER |
|
| 09/13/2007 | BUILDING - FINAL | Cancelled | IVRS - RI canceled |