Permit: T07CM01956

Parcel: 141096520

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
07/10/2007 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
06/14/2007 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) FIND DETAIL PAGE D1 OR HAVE PAGE DELETED
2) OK TO DRY IN AND WRAP
06/11/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
Items 2,4,6 & 7 from 6/5/07 and 6/7/07 not done
No ladder access to roof
Refee
06/06/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEMS 3, 4, 6 & 7 FROM 6/5/07 NOT DONE
2) NO LADDER ACCESS TO ROOF
06/05/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) KNEE BRACES NOT NAILED
2) ROOF NOT COMPLETE
3) GABLE END TRUSS NOT CLIPPED AT PORCH COLUMN
4) SHEAR 8 FT SEAMS NOT NAILED
5) NAIL PROTECT PLUMBING
6) D-1 PAGE MISSING, NEED DETAILS 1-8
7) STRAP DBL TOP PLATE SPLICES LESS THAN 4 FEET SEPERTATION ON IN AND OUTSIDE