Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T07CM01955
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/18/2007 | FRAMING | Approved | IVRS - Inspection :* | |
07/11/2007 | FRAMING | Partial Approval | IVRS - Inspection :* 1) OK TO INSULATE AND DRYWALL 2) PROVIDE CITY APPROVAL OF TRUSS REPAIR DOCUMENT |
|
07/10/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HAVE CG05 TRUSS REPAIR APPROVED BY CITY OF TUCSON FOR THIS ADDRESS 2) 5/D3 NOT COMPLIED WITH AT MBR SHEARWALL-MUST USE 16D NAILS |
|
07/06/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEMS 3, 4, 6 & 7 FROM PRIOR INSPECTION NOT DONE |
|
07/03/2007 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1. ITEMS 3, 4, 6, 7, 8, 10 FROM PRIOR INSP. NOT DONE STOPPED INSP. |
|
06/29/2007 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) UFER CLAMP INSPECTION MUD RING DOES NOT EXPOSE CLAMP-RELOCATE 2) CAULK STUCCO 3) SHEARWALL CONNECTION NOT PER 5/D3 4) HIP JACK TRUSSES CUT PROVIDE APPROVED REPAIR 5) SUPPORT HORIZONTAL DWV PLUMBING AT 4' ON CENTER REVERSE PITCH 6) NO INSULATION BEHIND TUBS 7) A/C COPPER OUT OF WALL 8) KITCHEN DIRTY ARM HAS WEIR HIGHER THAN VENT OPENING 9) MISSING MASTER TOILET 3" CLEANOUT 10) HOLDOWN NUTS LOOSE 11) STOPPED INSPECTION-TOO MANY ITEMS |