Permit: T07CM01955

Parcel: 141096530

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T07CM01955

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
12/18/2007 FRAMING Approved IVRS - Inspection :*
07/11/2007 FRAMING Partial Approval IVRS - Inspection :*
1) OK TO INSULATE AND DRYWALL
2) PROVIDE CITY APPROVAL OF TRUSS REPAIR DOCUMENT
07/10/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HAVE CG05 TRUSS REPAIR APPROVED BY CITY OF TUCSON FOR THIS ADDRESS
2) 5/D3 NOT COMPLIED WITH AT MBR SHEARWALL-MUST USE 16D NAILS
07/06/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEMS 3, 4, 6 & 7 FROM PRIOR INSPECTION NOT DONE
07/03/2007 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1. ITEMS 3, 4, 6, 7, 8, 10 FROM PRIOR INSP. NOT DONE

STOPPED INSP.
06/29/2007 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) UFER CLAMP INSPECTION MUD RING DOES NOT EXPOSE CLAMP-RELOCATE
2) CAULK STUCCO
3) SHEARWALL CONNECTION NOT PER 5/D3
4) HIP JACK TRUSSES CUT PROVIDE APPROVED REPAIR
5) SUPPORT HORIZONTAL DWV PLUMBING AT 4' ON CENTER REVERSE PITCH
6) NO INSULATION BEHIND TUBS
7) A/C COPPER OUT OF WALL
8) KITCHEN DIRTY ARM HAS WEIR HIGHER THAN VENT OPENING
9) MISSING MASTER TOILET 3" CLEANOUT
10) HOLDOWN NUTS LOOSE
11) STOPPED INSPECTION-TOO MANY ITEMS