Permit: T07CM01952

Parcel: 141096480

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T07CM01952

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
06/21/2007 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
06/20/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE 8/D-1 DETAIL FOR GARAGE FRONT
2) RAFTER SPACED MORE THAN 24" ON CENTER OVER FRONT BEDROOM
3) RAFTER NOTCHED MORE THAN 25 PERCENT OVER FRONT BEDROOM
4) ROOF SHEATHING MUST SPAN 3 TRUSSES (2 BAYS)
5) OSB ROOF SHEATHING MUST BE INSTALLED WITH GRAIN PERPENDICULAR TO TRUSSES
6) SOME AREAS OF ROOF NOT NAILED