Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T07CM01911

Parcel: 12709011E

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
09/11/2007 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
08/22/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
NEED TO SEE RELOCATED REFER LINES
OK CEILING TILES BRINK LAB #646, 642, 640, 634
08/15/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK FOR CEILING TILES PHASE 1 & 2