Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T07CM01911

Parcel: 12709011E

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM01911

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/01/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
NOTE: TEST BENCHES HAVE BEEN DISMANTLED - IF REASSEMBLED A CERTIFICATION WILL BE NEEDED - INSPECTOR RESERVES RIGHT OF REINSPECTION AT A LATER DATE.
09/27/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
09/24/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. EXIT LIGHT TO BE ON CIRCUIT AS SERVED 700.12
ALSO (1) NOT WORKING
2. VERIFY LISTING FOR ELECTRIC WORK TABLES
3. TIGHTEN FLEX FITTINGS
4. ID GROUNDING CONDUCTORS
5. CONDUCTORS IN RACEWAYS #8 & SMALLER TO BE CORRECT COLORS
6. SECURE TRANSFORMER TO STRUCTURE
7. SUPPORT MC CABLE AS PER CODE
8. INSTALL MAIN BONDING JUMPER AT TRANSFORMER
9. BOND RACEWAY FOR TRANSFORMERS

RECEIVED LETTER FOR M/C CABLE