Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01911
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/01/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* NOTE: TEST BENCHES HAVE BEEN DISMANTLED - IF REASSEMBLED A CERTIFICATION WILL BE NEEDED - INSPECTOR RESERVES RIGHT OF REINSPECTION AT A LATER DATE. |
|
09/27/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
09/24/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. EXIT LIGHT TO BE ON CIRCUIT AS SERVED 700.12 ALSO (1) NOT WORKING 2. VERIFY LISTING FOR ELECTRIC WORK TABLES 3. TIGHTEN FLEX FITTINGS 4. ID GROUNDING CONDUCTORS 5. CONDUCTORS IN RACEWAYS #8 & SMALLER TO BE CORRECT COLORS 6. SECURE TRANSFORMER TO STRUCTURE 7. SUPPORT MC CABLE AS PER CODE 8. INSTALL MAIN BONDING JUMPER AT TRANSFORMER 9. BOND RACEWAY FOR TRANSFORMERS RECEIVED LETTER FOR M/C CABLE |