Permit: T07CM01911

Parcel: 12709011E

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM01911

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/01/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/27/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
08/28/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO TILE
1. WAITING ON LETTERS
08/27/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROVIDE MANUFACTURES INSTRUCTIONS FOR GROUNDING OF MC CABLE
2. PROVIDE A LETTER AUTHORIZING USAGE OF ALUMINUM GROUNDING EQUIPMENT CONDUCTOR OF MC CABLE
3. FINISH #3, #4, #5 PREVIOUS INSPECTION

OK WALL VESTIBULE 600
08/24/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. USE APPROVED STRAPS TO SECURE MC CABLE
2. BOX OVERFILLED
3. SUPPORT VDV CABLING
4. FILL UNUSED OPENINGS
5. CHECK SUPPORT OF GROUND WIRE TO GRID
08/21/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK MAIN HALLWAYS & BRINK LAB
08/20/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) FINISH PREVIOUS ITEMS 1,2, 4 & 6
08/15/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. SECURE VDV CABLES UPON EXITING OF CABLE TRAY
2. ELECTRICAL SUPPORTED TO BE AS PER 300.11
3. ATTACH FIXTURES TO GRID 410.16
4. SUPPORT WIRES TO BE TO STRUCTURE
5. EXISTING AC DISCONNECTS HAVE NO BOND AT
CONCENTRIC 250.97
6. SUPPORT VDV OFF OF CEILING TILES 800.6, 725.6
7. SUPPORT WIRES FOR EXIT LIGHTS
07/24/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROTECT M/C CABLE IN SHALLOW STUDS
2. STRAP M/C CABLE ABOVE BOXES CUT OPEN

OK WALLS