Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/24/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* EXHAUST DUCT NOT PROPERLY CONNECTED OK TO INSTALL TILES |
|
| 06/20/2008 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ALL LONG & TRANSVERSE JOINT TO BE SEALED PER PLANS REMOVE DUCT WRAP FOR INSPECTION 2. FLEX SUPPORTS NOT TO EXCEED 4' PER PLANS 3. FLEX SUPPORTS TO BE MIN. 26 GALE S.M PER PLANS 4. FLEX RADIUS NOT TO EXCEED 1.5 PER PLANS 5. BRANCH TAKE OFFS TO BE 45 DEG. PER PLANS 6. FLEX DUCT NOT TO EXCEED 8' PER PLANS 7. ALL RETURN CANS TO BE INSULATED |
|
| 06/19/2008 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* PROPERLY SUPPORT CONDENSATE PIPING IN SHOWROOM |