Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/10/2007 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 10/04/2007 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO GROUND SYSTEM-YOU MUST INSTALL TWO 8 FOOT LONG GROUND RODS SIX FEET APART AND CONNECT TO SERVICE PANEL WITH A CONTINOUS ? COPPER WIRE 2) NO ADDRESS ON PANEL 3) NO 20 AMP GFCI MAINTENANCE OUTLET-SEE PAGE 8 OF PLAN |