Permit: T07CM01895

Parcel: 105110690

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
10/03/2007 MECHANICAL - ABOVE CEILING Approved
09/27/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
- PROVIDE SAFETY WIRES TO ALL REGISTERS IN SUSPENDED CEILING
- AUDIBLE & VISUAL ALARM TO BE INSTALLED PRIOR TO FINAL INSPECTION
09/20/2007 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DUCT SYSTEM NOT SIZED OR INSTALLED PER PLAN
2) PROVIDE A CONDENSATE DRAIN PER PLANS
3) SUPPORT DIFFUSERS
4) PROVIDE AUDIBLE AND VISIBLE ALARM FOR DUCT SMOKE DETECTOR