Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T07CM01894
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/16/2007 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 07/12/2007 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) OK TO COVER EXT. WALLS AND ROOF 2) NOTE: AT INTERMEDIATE, CHECK TWO RETROS 3) SHEAR TRANSFER PANELS NAIL BLK TO BLK |
|
| 07/09/2007 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FRONT OF GARAGE AND STHD 14 TO MUCH SPAULING, NEED RETRO, SEE #3 OPT ON P. TENSION PLATE 2) BRING EXTRA STUDS (FOR PT. LOAD OF GLU LAM) DOWN TO CONC. 3) ROOF FRAME GIRDER TRUSS TO GIRDER, HGUS26, USE 16D SINKERS AT TOE NAIL, NOT 2 1/2" 16 4) WALKING DECK NOT SECURED 5) NEED WIND BRACE 2ND FLOOR S/EAST 6) 5'-0" LONG CS STRAPS AT FRONT AND REAR OF ROOF, SEE PLAN 7) 89A/SD3 AND 90/SD3 NOT PER PLAN 8) MARKED IN BLACK, MISSED NAILING ON ROOF, OSB TURNED WRONG WAY 9) CABLES NOT PULLED |