Permit: T07CM01894

Parcel: 141313200

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T07CM01894

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
08/16/2007 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
07/12/2007 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) OK TO COVER EXT. WALLS AND ROOF
2) NOTE: AT INTERMEDIATE, CHECK TWO RETROS
3) SHEAR TRANSFER PANELS NAIL BLK TO BLK
07/09/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FRONT OF GARAGE AND STHD 14 TO MUCH SPAULING, NEED RETRO, SEE #3 OPT ON P. TENSION PLATE
2) BRING EXTRA STUDS (FOR PT. LOAD OF GLU LAM) DOWN TO CONC.
3) ROOF FRAME GIRDER TRUSS TO GIRDER, HGUS26, USE 16D SINKERS AT TOE NAIL, NOT 2 1/2" 16
4) WALKING DECK NOT SECURED
5) NEED WIND BRACE 2ND FLOOR S/EAST
6) 5'-0" LONG CS STRAPS AT FRONT AND REAR OF ROOF, SEE PLAN
7) 89A/SD3 AND 90/SD3 NOT PER PLAN
8) MARKED IN BLACK, MISSED NAILING ON ROOF, OSB TURNED WRONG WAY
9) CABLES NOT PULLED