Permit: T07CM01886

Parcel: 11451142A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM01886

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/26/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
MC TO BE SUPPORTED AS PER 330.30 & 300.11
07/20/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. FINISH #4 OF INSPECTION DATED 6/21/07
2. PLEASE USE QUALIFIED ELECTRICAL PERSONNEL
07/16/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. SUPPORT WIRES ARE NEEDED FOR FIXTURES -- 2 ON OPPOSITE CORNERS -- ALSO, ATTACH TO GRID 2 SCREWS ON CENTER OR 4 ON CORNERS 410.16
2. FINISH #4, 5, 6 OF PREVIOUS INSPECTION
06/21/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CORD NOT ALLOWED AS PERMANENT WIRING FOR LIGHTS
ALSO, LIGHTS TO BE LISTED FOR CORD & PLUG CONNECTION AREA TO HAVE PERMANENT LIGHTING.
2. LABEL BREAKERS AS PER 408.4
3. BATHROOM RECEPTACLE TO BE GFCI PROTECTED
4. SUPPORT M/C CABLES ABOVE CEILING AS PER CODE
5. FILL UNUSED OPENINGS IN JUNCTION BOXES
6. PLEASE ADD SUITE # TO PERMIT
06/20/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
CANNOT LOCATE SPACE - NO SUITE # POSTED