Permit: T07CM01881
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/30/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/27/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. RE-IDENTIFY WHITE WIRES USED AS SWITCH LEGS 2. INSTALL SEISMIC WIRES ON EXIT LIGHTS 3. OK TO CLOSE CEILING WILL CHECK THESE ITEMS AT FINAL |
|
| 07/26/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK GROUNDING ELECTRODE CONDUCTOR INSTALLATION |
|
| 07/25/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK TO INSTALL CUTS IN CEILING GROUND LEAVE REST OF CEILING OPEN-NOT READY FOR INSPECTION 2) OK TO CLOSE WALL AT PANEL 3) INSTALL GFCI FROM NEUTRAL BAR AT SERVICE DISCONNECT TO GROUNDING ELECTRODE BAR IN SERVICE ROOM 4) RECEIVED LETTERS FOR USE OF MC AND ? PLUG IN PANEL |
|
| 07/18/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PROPERLY SUPPORT CONDUIT & CABLES ABOVE PANEL 2. PLANS CALL FOR BOLT ON PANEL -- WE HAVE PLUG IN 3. IS USED EQUIPMENT ALLOWED ON THIS JOB 4. PLEASE VERIFY IF M/C CABLE IS ALLOWED |
|
| 07/13/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK WALLS 2. DO NOT SHEETROCK OVER PANEL. WIRING NOT COMPLETE TO PANEL & NEEDS TO BE INSPECTED. |
|
| 07/11/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. NEED FOR SIDE SUPPORT ON BOXES 2. RMS 9, 10, 11, 12 NOT READY 3. OK TO INSULATE RECALL BEFORE SHEETROCKING TO CHECK BOX SUPPORT |