Permit: T07CM01881

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/30/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/27/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. RE-IDENTIFY WHITE WIRES USED AS SWITCH LEGS
2. INSTALL SEISMIC WIRES ON EXIT LIGHTS
3. OK TO CLOSE CEILING WILL CHECK THESE ITEMS AT FINAL
07/26/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK GROUNDING ELECTRODE CONDUCTOR INSTALLATION
07/25/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TO INSTALL CUTS IN CEILING GROUND LEAVE REST OF CEILING OPEN-NOT READY FOR INSPECTION
2) OK TO CLOSE WALL AT PANEL
3) INSTALL GFCI FROM NEUTRAL BAR AT SERVICE DISCONNECT TO GROUNDING ELECTRODE BAR IN SERVICE ROOM
4) RECEIVED LETTERS FOR USE OF MC AND ? PLUG IN PANEL
07/18/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PROPERLY SUPPORT CONDUIT & CABLES ABOVE PANEL
2. PLANS CALL FOR BOLT ON PANEL -- WE HAVE PLUG IN
3. IS USED EQUIPMENT ALLOWED ON THIS JOB
4. PLEASE VERIFY IF M/C CABLE IS ALLOWED
07/13/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK WALLS
2. DO NOT SHEETROCK OVER PANEL. WIRING NOT COMPLETE TO PANEL & NEEDS TO BE INSPECTED.
07/11/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. NEED FOR SIDE SUPPORT ON BOXES
2. RMS 9, 10, 11, 12 NOT READY
3. OK TO INSULATE
RECALL BEFORE SHEETROCKING TO CHECK BOX SUPPORT