Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/26/2007 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 07/24/2007 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) GARAGE FRONT HOLDOWNS NOT INSTALLED 2) OK TO DRY IN ROOF AND EXTERIOR EXCEPT GARAGE FRONT |
|
| 07/23/2007 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) GARAGE HOLDOWNS NOT IN 2) 4 EACH #6 HOLDOWNS MISSING 3) OK TO DRY IN ROOF AND ALL BUT GARAGE AND BEDROOM FRONT TO CHECK HOLDOWNS |
|
| 07/10/2007 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEMS 1, 2, 4 & 6 FROM 6/22/07 NOT COMPLIED WITH |
|
| 07/03/2007 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COVERED WITHOUT APPROVAL. REMOVE ALL LATHE 2. (2) NO OSHA APPROVED LADDER ACCESS TO ROOF 3. NO PLAN/PERMIT ON SITE |
|
| 06/22/2007 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) #5 HOLDOWNS NOT INSTALLED 2) INTERSECTING SHEARWALLS MUST COMPLY WITH 5/DT1 3) PORCH LEDGER NOT CLIPPED PER 9/DT1 4) PROVIDE APPROVED DETAIL FOR MISSING SHEARWALL 5 WITH OPTIONAL DINING ROOM 5) H2.5 CLIPS MISSING AT LEDGER AT BEARING SHEARWALL BREAK IN M/BR 6) LADDER MUST EXTEND AT LEAST 30" ABOVE ROOF EDGE. NO ROOF INSPECTION. YOU MUST PROVIDE SAFETY SPOTTER FOR 2 STORY ROOF INSPECTION 7) SHEARWALL 5 REQUIRES A35 CLIPS AT 16" ON CENTER 8) 13/DT1 REQUIRES 3-2 X 6 KING STUDS AND 2-2 X 45 USED 9) STOPPED INSPECTION-TOO MANY ITEMS |