Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
07/26/2007 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
07/24/2007 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) GARAGE FRONT HOLDOWNS NOT INSTALLED
2) OK TO DRY IN ROOF AND EXTERIOR EXCEPT GARAGE FRONT
07/23/2007 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) GARAGE HOLDOWNS NOT IN
2) 4 EACH #6 HOLDOWNS MISSING
3) OK TO DRY IN ROOF AND ALL BUT GARAGE AND BEDROOM FRONT TO CHECK HOLDOWNS
07/10/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEMS 1, 2, 4 & 6 FROM 6/22/07 NOT COMPLIED WITH
07/03/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. COVERED WITHOUT APPROVAL. REMOVE ALL LATHE
2. (2) NO OSHA APPROVED LADDER ACCESS TO ROOF
3. NO PLAN/PERMIT ON SITE
06/22/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) #5 HOLDOWNS NOT INSTALLED
2) INTERSECTING SHEARWALLS MUST COMPLY WITH 5/DT1
3) PORCH LEDGER NOT CLIPPED PER 9/DT1
4) PROVIDE APPROVED DETAIL FOR MISSING SHEARWALL 5 WITH OPTIONAL DINING ROOM
5) H2.5 CLIPS MISSING AT LEDGER AT BEARING SHEARWALL BREAK IN M/BR
6) LADDER MUST EXTEND AT LEAST 30" ABOVE ROOF EDGE. NO ROOF INSPECTION. YOU MUST PROVIDE SAFETY SPOTTER FOR 2 STORY ROOF INSPECTION
7) SHEARWALL 5 REQUIRES A35 CLIPS AT 16" ON CENTER
8) 13/DT1 REQUIRES 3-2 X 6 KING STUDS AND 2-2 X 45 USED
9) STOPPED INSPECTION-TOO MANY ITEMS