Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2007 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/11/2007 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTE: - SECURE EXHAUST DUCT AT ROOF PENETRATION WITH "SHEET METAL STRAP" - VERIFY ALL SHEETMETAL (PLENUMS) AND PROVIDE R4.2 INSULATION IN ALL AREAS - PROVIDE TAPE ON ANY CONNECTION - RELOCATE FLEX DUCT TO SUPPLY BATHROOM ON UNIT 1 (AFTER DRYWALL INSTALLATION FLEX DUCT NOT HAVE SPACE AND CAPACITY 6" DIA.) - RELOCATE FLEX DUCT TO SUPPLY KITCHEN, EXHAUST FOR RANGE DOES NOT HAVE SPACE FOR DUCT 5" DIA. DUCT THRU ROOF ON BOTH UNITS - PROVIDE SPECIFICATION FOR INSULATION IN COMPLIANCE FOR R4.2 |
|
| 07/10/2007 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PROVIDE A SCREW IN EXHAUST DUCT CONNECTION TO FAN - SECURE EXHAUST DUCTS AT ROOF PENETRATED WITH SHEETMETAL STRAP. - INSULATE ALL SHEETMETAL BOXES & PLENUM WITH R4.2 INSULATION. - 1/2" DUCT LINER IS R2 - RELOCATE THE ELEC. WIRES SMASHING THE 6" DUCT TO BATHROOM UNIT 1 - REMOVE SCREEN FROM DRYER VENT T-TOPS - PROVIDE SCREEN IN EXHAUST T-TOPS - ON FINAL BE SURE EXPOSED DUCT OUTDOORS HAS R8 INSULATION |