Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
07/12/2007 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
07/11/2007 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTE:
- SECURE EXHAUST DUCT AT ROOF PENETRATION WITH "SHEET METAL STRAP"
- VERIFY ALL SHEETMETAL (PLENUMS) AND PROVIDE R4.2 INSULATION IN ALL AREAS
- PROVIDE TAPE ON ANY CONNECTION
- RELOCATE FLEX DUCT TO SUPPLY BATHROOM ON UNIT 1
(AFTER DRYWALL INSTALLATION FLEX DUCT NOT HAVE SPACE AND CAPACITY 6" DIA.)
- RELOCATE FLEX DUCT TO SUPPLY KITCHEN, EXHAUST FOR RANGE DOES NOT HAVE SPACE FOR DUCT 5" DIA. DUCT THRU ROOF ON BOTH UNITS
- PROVIDE SPECIFICATION FOR INSULATION IN COMPLIANCE FOR R4.2
07/10/2007 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PROVIDE A SCREW IN EXHAUST DUCT CONNECTION TO FAN
- SECURE EXHAUST DUCTS AT ROOF PENETRATED WITH SHEETMETAL STRAP.
- INSULATE ALL SHEETMETAL BOXES & PLENUM WITH R4.2 INSULATION.
- 1/2" DUCT LINER IS R2
- RELOCATE THE ELEC. WIRES SMASHING THE 6" DUCT TO BATHROOM UNIT 1
- REMOVE SCREEN FROM DRYER VENT T-TOPS
- PROVIDE SCREEN IN EXHAUST T-TOPS
- ON FINAL BE SURE EXPOSED DUCT OUTDOORS HAS R8 INSULATION