Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/09/2007 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 10/31/2007 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED WAIVER BY BLDG OFFICIAL TO GO OVERHEAD WITH SERVICE |