Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T07CM01838

Parcel: 115024690


Addresses:

317 E DRACHMAN ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/01/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/28/2007 ELECTRIC - FINAL Cancelled IVRS - RI canceled
09/25/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. OLD SERVICE EQUIPMENT CANNOT BE USED AS SUB-PANEL
PANEL MARKED SUITABLE FOR USE ONLY AS RESIDENTIAL SERVICE EQUIPMENT - NEC 110.3
2. BROKEN/CUT STRANDS ON EQUIPMENT GROUNDING CONDUCTOR TO PANEL
3. PROPERLY MARK BREAKER IN SERVICE EQUIPMENT TO SUB-PANEL NEC 408.4
09/21/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
EQUIPMENT TO BE OPEN FOR INSPECTION
I DO NOT HAVE A SOCKET SET
09/05/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SERVICE RISER NOT TO PROTRUDE INTO THE SPACE REQUIRED FOR CLEARANCE IN FRONT OF SERVICE (36") DOWN TO GRADE -- NEC 110.26
08/29/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SERVICE RISER BLOCKING FRONT ENTRY WORKING CLEARANCE - NEC 110.26
ALSO, CORRUGATED RACEWAY (ORANGE)