Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01838
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/01/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
09/28/2007 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
09/25/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. OLD SERVICE EQUIPMENT CANNOT BE USED AS SUB-PANEL PANEL MARKED SUITABLE FOR USE ONLY AS RESIDENTIAL SERVICE EQUIPMENT - NEC 110.3 2. BROKEN/CUT STRANDS ON EQUIPMENT GROUNDING CONDUCTOR TO PANEL 3. PROPERLY MARK BREAKER IN SERVICE EQUIPMENT TO SUB-PANEL NEC 408.4 |
|
09/21/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* EQUIPMENT TO BE OPEN FOR INSPECTION I DO NOT HAVE A SOCKET SET |
|
09/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SERVICE RISER NOT TO PROTRUDE INTO THE SPACE REQUIRED FOR CLEARANCE IN FRONT OF SERVICE (36") DOWN TO GRADE -- NEC 110.26 |
|
08/29/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SERVICE RISER BLOCKING FRONT ENTRY WORKING CLEARANCE - NEC 110.26 ALSO, CORRUGATED RACEWAY (ORANGE) |